2014年10月10日星期五

LED High Bay Fluorescent Vs T8 & T5HO Fluorescent & Metal Halide

LED High Bay Fluorescent Vs T8 & T5HO Fluorescent & Metal Halide





Choose the right lighting solution on your top ceiling environment. Saving more cost in maintenance and electricity. 

Let us know more details below 


T8T5MH                                    LEDT8
Energy Efficiency
85lm/w
90lm/w
77lm/w
110lm/w
Life Expectancy
10000-16000h
20000-30000h
10000-16000h
30000h
Initial Cost
High
High
Low
High
Cost of Maintenance
High
Low
High
Low
Temperature Performance
Poor
Poor start at low temperature, low lumen output when outside of range 20-45C
Good
Very Good
Color
Good
Good
Moderate to Good
Good
Light Distribution
Moderate to Good
Moderate to Good
Good
Moderate to Good
Lamp Lumen Loss overlifetime
High
Low
High
Low
Dimming control
None
Good 0-10v
None
Good: 0-10v
On/Off Control
Need  50s delay
Instant On/Off
Need 15 min delay
Instant On/Off
High Bay Retrofit Applications
Moderate
Moderate
N/A
Good
Low Bay Applications
Moderate
Moderate
Moderate
Good
Parking Garage Applications
Moderate
Moderate
Moderate
Good
Area Lighting Applications
Moderate
Moderate
Moderate
Good
Mercury
Yes
Yes
Yes
None

As shown in below table, a 4-lamp F54 T5HO fixture can replace a 400w MH fixture, for example, and save about 50% on energy while producing about 20% less maintained light output. A 6-lamp LED T8 fixture can replace the same 400W MH and save about 50% on energy while producing about 16% less maintained light output.








MH with Magnetic Ballast
T8 Lighting Systems
T5HO Lighting Systems
LED T8 Lighting Systems
No. Lamps
400w Probe-start MH
8  F32T8 Fluorescent
4 F54 T5HO Fluorescent
 X 30W LED T8
Service Life
20,000hours@ 10hours/start
20,000 hours@ 10hours/start
24,000hours@ 10hours/start
30,000hours/10hours/start
Initial lamp light output
360000lm
18000lm
20000lm
19800lm
Ballast
Probe-start Magnetic
Instant start
Program start
NO
Ballast Factor
1.0
1.0
1.0
No
Lamp Watts
400w
256w
216w
183w
System Watts
458w
286w
234w
183w
Relative System  Watts
100%
64%
51%
46%
Initial system efficacy
79lm/w
85lm/w
85lm/w
110lm/w
Lumen Maintenance
65%
95%
95%
98%
Mean Lumens
23400lumens@40% of lamp life
17100lumens @ 40% of lamp life
19000lumens @ 40% of lamp life
19404lumens @ 40% of lamp life
Relative maintained light output
100%
73%
81%
83%
Maintained system efficacy
51lm/w
81lm/w
81lm/w
108lm/w
Color rendering
65CRI
82-85CRI
82-85CRI
85CRI
Starting Time
4 minutes
<1.5seconds
<1.5 seconds
<1second
Re-strike Time
10 minutes
<1.5seconds
<1.5 seconds
<1second
Color temperature
3000-4000K
3000-5000K
3000-5000K
3000-5000K
Mercury
Yes
Yes
Yes
None
5years Electricity cost
US$125500
US$78300
US$64100
US$50000




Cost comparison – e.g. 100set project, working @ 10hrs/day, electricity cost US$0.15/KWH
MH with Magnetic Ballast
T8 Lighting Systems
T5HO Lighting Systems
LED T8 Lighting Systems
No. Lamps
400w Probe-start MH
8  F32T8 High LumenFluorescent
4 F54 T5HO Fluorescent
 X 30W LED T8
System Watts
458w
286w
234w
183w
Service Life
20,000hours@ 10hours/start
24,0000 hours@ 10hours/start
24,000hours@ 10hours/start
30,000hours/start
Initial investment
US$18000
US$24000
US$20000
US38000
1st  year electricity cost
458*10*365/1000w*0.15=251
286*10*365/1000*0.15=156.6
234*10*365/1000*0.15=128.2
183*10*365/1000*0.15=100
…………
5th year electricity cost
458*10*365/1000w*0.15*5=1255
286*10*365/1000*0.15*5=783
234*10*365/1000*0.15*5=641
183*10*365/1000*0.15*5=500
Ballast and bulbsMaintenance/2years

US$50
US$30
US$30
 None
5year Labor Maintenance
US$100
US$50
US$50
None
2nd investment
US$900
US$






•T8 Vs. T5HO: Regarding fluorescent, the choice is T5HO or LED T8. Lighting professionals may hear that T8 fixtures are better at fixture heights <20 ft., T5HO at >20 ft., and either T8 or T5HO at 18-25 ft. mounting heights. However, while T5HO may produce “glare bombs” at lower mounting heights, both T8 and T5HO can be used in high- and low-bay applications.

•T5HO lamps produce about twice the light output of a standard T8 or T12 lamp in approximately the same length and a fraction of the diameter, making them very bright. While they produce less light than a standard MH lamp, they have 95 percent lumen maintenance compared to 65 percent for a standard MH. This means a six-lamp F54T5HO system produces about 83 percent of the initial light output of a 400W MH lamp, but 121 percent of its light output at 40 percent of lamp life.

•For bay applications, standard T8 lamps are generally not used. Instead, F32T8HO, or Super T8, are used. Super T8 lamps produce 3100+ lumens; when operated on a high ballast factor (1.15) ballast, this system can produce 3,565 lumens, 71 percent of the light output of a comparable F5

4T5HO system.

•Besides light output, ease of replacement should be considered. To get higher light output from a T8 fixture, Super T8 lamps should be specified, but the owner may substitute to lower-output (and less expensive) T8 lamps that may be used elsewhere in the facility such as offices. This will result in lower light levels than expected. T5HO and Super T8 lamps are typically offered only by electrical distributors.

•T5HO and T8 lamps are sensitive to ambient temperature in the fixture’s ballast compartment. T5HO is designed to operate optimally at higher temperatures (35 oC or 95 oF) and T8 at lower temperatures (25 oC or 77 oF).

•In addition, the presence of occupancy sensors and other switching strategies is a factor in whether to choose T8 or T5HO. If occupancy sensors are used and the lamps are frequently switched, lamp degradation will occur after 12,000 to 15,000 switching cycles on a T8 lamp operated on an instant start electronic ballast, the most common T8 ballast type. Some lamp manufacturers may not warranty their T8 lamps when operated on instant start ballasts and controlled by occupancy sensors. Super T8 lamps, however, are rated to last 4,000 hours longer than T5HO lamps.


On the other hand, T5HO lamps are operated with programmed start ballasts, which are generally more expensive and are wired in series or series-parallel compared to parallel for instant start ballasts.

More information about the led high bay fluorescent, please contact us by sales@bomaxs.com